Detectors
2 conductors wire 22 AWG.
Maximum length: 100 meters
Do not apply voltage higher than 30VAC/DC to alarm inputs.
Relays for Door lock
2 conductors wire 18 AWG.
Standard length: 10 meters. For more than 10m, depends on wire resistance and load current consumption
WARNING: always fit a Diode across a DC electric lock, at the lock end.
RELAYS RATING: max. 24V AC/DC-1A OR 12V AC/DC-2A
Card Readers
Electronic cable, NOT twisted, 8 wires, 22AWG (Such as BELDEN 9421)
Maximum distance from the controller to reader: 100 meters (50 meters for magnetic readers)
Biometric Readers
Electronic cable, NOT twisted, 15 wires, 22AWG (Such as BELDEN 8458)
The maximum distance from the controller to the reader: 100 meters
RS485
Twisted pair cable 24AWG.
The AWG (also called "Gage") defines the copper diameter.
Best cable for installations in a noisy environment is:
Braided copper shielded twisted pair cable 24AWG - BELDEN part number 9841
Link all the RS485 wire shields together and connect it at only the RS232/RS485 interface end (not at the controller end) and use a very good earth at the interface.
The maximum distance of the RS485 bus: 1200 meters
If the bus needs to run over a long distance (approx. 400m or more), consider installing a 120Ohm resistor as a terminator at the last (most distant) controller.
RS232
The maximum distance from the controller to the PC: 10 meters
TCP/IP
Cat5 cable
Comments
0 comments